HVJB 125 11 kV high voltage cabinet
The HVJB 125 high-voltage cabinet is a unique solution for terminating offshore cable or above-ground distribution systems. Connections up to 11 kV are installed in the power conductor compartment. A separate control compartment is used to lead out fibre optic or control cables.
- Working with optical fibres or control conductors without HV source insulation
- Each compartment independent IP66
- Fault 45 kA for 0.2 seconds
- DTS-01 tested box
- Large range of colours and surface finishes
Types of cabinets
|
Product type |
HVJB1253(x-x)LH |
|
Control location |
on the left |
|
Width (mm) |
1200 |
|
Height (mm) |
1250 |
|
Depth (mm) |
314 |
|
Power (W)** |
346/173 |
|
Max. voltage (kV) |
11 |
|
Max. current (A) |
980 |
|
Max. number of lines |
3 |
|
Weight (kg) |
130 |
|
Product type |
HVJB1254(x-x)LH |
|
Control location |
on the left |
|
Width (mm) |
1200 |
|
Height (mm) |
1250 |
|
Depth (mm) |
314 |
|
Power (W)** |
346/173 |
|
Max. voltage (kV) |
11 |
|
Max. current (A) |
980 |
|
Max. number of lines |
4 |
|
Weight (kg) |
130 |
|
Product type |
HVJB1253(x-x)RH |
|
Control location |
on the right |
|
Width (mm) |
1200 |
|
Height (mm) |
1250 |
|
Depth (mm) |
314 |
|
Power (W)** |
346/173 |
|
Max. voltage (kV) |
11 |
|
Max. current (A) |
980 |
|
Max. number of lines |
3 |
|
Weight (kg) |
130 |
|
Product type |
HVJB1254(x-x)RH |
|
Control location |
on the right |
|
Width (mm) |
1200 |
|
Height (mm) |
1250 |
|
Depth (mm) |
314 |
|
Power (W)** |
346/173 |
|
Max. voltage (kV) |
11 |
|
Max. current (A) |
980 |
|
Max. number of lines |
4 |
|
Weight (kg) |
130 |
* * *(x-x) reduces the number of connectors per phase, 1st position = top, 2nd position = bottom. For example: HVJB73 (2-1) = 2 x conductors per phase top input and 1 x conductor per phase input.
** The power rating is determined by the ambient temperature range: -20 to +400C / -50 to +550C respectively. A higher power rating can also be achieved if the enclosure is labelled Ex e IIC T150°C Gb.
Standard technical specifications
|
Enclosure type |
High-voltage |
|
IP protection |
IP66/67 |
|
Material |
Stainless steel (EN 1.4404) |
|
External temperature |
-20°C to +40°C or -50°C to +55°C |
|
Maximum inputs |
3 for incoming phase & 3 for outgoing phase |
|
Crimping lugs |
from 16 mm2 to 1000 mm2 |
|
Earthing |
Through the studs on the housing |
|
Mounting |
Through mounting tapes 3 mm |
|
Certification |
|
|
Zone Classification |
Zone 1 & 21, Gas and Dust |
|
Type of protection |
Ex e (Increased protection), Ex tb (Dust protection), Ex op is |
|
Hardware encoding |
Ex e IIC T4 Gb, Ex tb IIIC T70°C Db |
|
Ex e IIC T150°C Gb, Ex tb IIIC T110°C Db |
|
|
Certificate number |
HV – CML16ATEX3324 |
|
FO – CML14ATEX3123X |
|
Product design and specifications are subject to change without notice; please check the website for the latest specifications
Options
|
ACH |
Anti-condensation heater |
|
EP |
Polished |
|
RALxxxx |
Epoxy powder coating |
|
MB |
Mounting rod for bolts |
Add the required suffix to the product reference.
Example: HVJB1253 (0-3) RHACH = HVJB 125, size 7, 3-way with 3 inputs at the bottom, compartment on the right side and anti-condensation heater.
Accessories
|
ABDM2010SS |
M20 Airway drainage |
|
ABDM2510SS |
M25 Airway drainage |
|
FBM12EEMS*** |
M12 Lifting bolts |
|
FBM16EEMS*** |
M16 Lifting bolts |
*** Stainless steel lifting bolts are also available, contact them for information