Explosion-proof PCS command devices made of polyester
PCS control stations are a range of cost-effective local control stations. Its modular design consists of four enclosures combined with multiple operators to maximise flexibility. A number of pre-configured solutions with the most commonly used modules are also available. Key feature:
- Universal contact block
- Corrosion resistant polyamide housing
- Cover with fixing screws
- May be related to the creation of large control stations
Standard technical specifications
|
IP level |
IP66 |
|
Enclosure material |
Body and cover made of polyamide |
|
Module material |
Corrosion-resistant polyamide |
|
External temperature |
‐40℃ to +40℃ |
|
Terminals |
Maximum 2.5mm2 |
|
Certification |
|
|
Zone Classification |
Zone 1 & 21, Gas & Dust |
|
Type of protection |
Controller with ammeter only: Ex e, Controller with switch and indicator lamp Ex de |
|
Hardware classification |
Ex e II T6, Ex tD A21 IP66 T80℃ Ex de IIC T6, Ex tD A21 IP66 T80 |
|
Certificate number |
DNV 12 ATEX 13746 |
|
Module type |
Button, Emergency stop button, Mushroom button, Key button |
|||
|
Utilisation category |
AC12 |
AC15 |
DC13 |
DC13 |
|
Maximum voltage |
250V |
250V |
110V |
24V |
|
Maximum current |
16A |
10A |
0.5A |
1A |
|
Module type |
Indicator lamp |
|||
|
Category of use |
AC15 |
DC13 |
||
|
Maximum voltage |
250V |
24V |
||
|
Maximum current |
6A |
1A |
||
|
Module type |
Button with indicator lamp |
|||
|
Category of use |
AC15 |
DC13 |
||
|
Maximum voltage |
240V |
24V |
||
|
Maximum current |
6A |
1A |
||
Product design and specifications are subject to change without notice; please check the website for the latest specifications
Ordering information