Explosion-proof linear luminaire ZFL

Explosion-proof linear luminaire ZFL

Explosion-proof linear luminaires of ZFL series are designed for illumination of industrial premises, open areas in oil, gas, chemical, cement, woodworking, metallurgical, pharmaceutical and other areas where the presence of explosive atmospheres is possible.

ZFL explosion-proof luminaires can also be equipped with an uninterruptible power supply (UPS) built into the luminaire housing. The operating time in emergency mode is 180min.

This series of luminaires is designed for installation in explosion hazardous areas of class 2, 22 and fire hazardous areas of classes P-I, P-II. It is also permissible to use it in class 21 zone in compliance with the requirements of NPAOP 40.1.1.32-01 “Electrical equipment of special installations”, “Technical Regulations of equipment and protective systems designed for use in potentially vibuhoneproof environment” and other normative documents.

CODE

LAMP TYPE

TEMPERATURE CLASS

EMERGENCY BLOCK

AUTONOMY

DRAWING

GAS

DUST

LIGHTS FOR ONE OR TWO LUMINEScent lamps – 110-240V AC 50/60Hz power supply

ZFL-118

1 x 18 W

T6 (AT = 40°C)

T85°C

А

T5 (AT = 50°C)

T100°C

T4 (AT = 60°C)

T135°C

ZFL-136

1 x 36 W

T6 (AT = 40°C)

T85°C

А

T5 (AT = 50°C)

T100°C

T4 (AT = 60°C)

T135°C

ZFL-218

2 х 18 W

T6 (AT = 40°C)

T85°C

A

T5 (AT = 50°C)

T100°C

T4 (AT = 60°C)

T135°C

ZFL-236

2 х 36 W

T6 (AT = 40°C)

T85°C

A

T5 (AT = 50°C)

T100°C

T4 (AT = 60°C)

T135°C

LIGHTS FOR ONE OR TWO LUMINESCENT LAMPS WITH EMERGENCY POWER SUPPLY – 220/240V AC 50/60Hz POWER SUPPLY

ZFLE-118

1 x 18 W

T6 (AT = 40°C)

T85°C

4.8 V – 4Ah

180 мин.

A

T5 (AT = 50°C)

T100°C

T4 (AT = 60°C)

T135°C

ZFLE-136

1 x 36 W

T6 (AT = 40°C)

T85°C

4.8 V – 4Ah

180 min.

A

T5 (AT = 50°C)

T100°C

T4 (AT = 60°C)

T135°C

ZFLE-218

2 х 18 W

T6 (AT = 40°C)

T85°C

4.8 V – 4Ah

180 min.

A

T5 (AT = 50°C)

T100°C

T4 (AT = 60°C)

T135°C

ZFLE-236

2 х 36 W

T6 (AT = 40°C)

T85°C

4.8 V – 4Ah

180 min.

A

T5 (AT = 50°C)

T100°C

T4 (AT = 60°C)

T135°C

Technical specifications

EXECUTION

II 3 G Ex nA IIC T6/T5/T4 Gc

II 3 D Ex tc IIIC T85°C/T100°C/ T135°C Dc

COMPLIANCE

EN 60079-0; EN 60079-15; EN 60079-31

LEVEL OF PROTECTION

IP66

OPERATING TEMPERATURE RANGE

-20°C ÷ +60°C

Mechanical characteristics

Body

glass fibre reinforced polyester resin, self-extinguishing in accordance with the following. UL94

diffuser

U/V resistant polycarbonate

Colour

powder-coated, epoxy, colour grey RAL-7039

Gaskets

EPDM 60 rubber is suitable for high temperatures and resistant to environmental conditions

Cable connection

ISO-2xM20 cable glands, ISO-2xM20 plugs

Electrical characteristics

Power supply

two-channel electronic ballast 110÷240B AC/DC 50/60Hz (cos ρ ≥ 0.98)

Cartridge

double pin G13

Wiring

cables with silicone insulation resistant to high temperatures

Terminals

for cable connection up to 4mm²

Accessories on request:

  • Mounting for mounting on linear support complete with stainless steel bolts;
  • Ceiling mount complete with stainless steel bolts;
  • Suspension mount complete with stainless steel bolts;
  • Wall mount complete with stainless steel bolts;
  • The voltage is different from the standard voltage;
  • The connection is different from the standard connection;
  • Emergency switch;

 

Thank you!

Your application has been successfully sent,
we will contact you shortly