Weather station (temperature regulator) Terneo sneg
Weather station (temperature regulator) Terneo sneg

Upper/lower temperature limits
(factory settings 5ºC/-10ºC)
To view the upper temperature limit, briefly press “+”, the lower limit – “-“. The flashing value of the borders can be changed with the “+” and “-” keys. 3 s after the last key press the controller returns to the normal operating mode
Functional menu
|
Function menu item |
Setting procedure |
Value on the screen |
Factory settings |
Change with the “+” and “-” keys |
|
Settings menu |
||||
|
Postheat time (postheat). After the end of precipitation, the heating will continue for the set value |
Hold down the middle key for 3 s. Navigate through the menu – middle key, change the parameter with “+” and “-“ |
Pht 2.0(two) H (hours) |
2 hours |
0.5-9 hours, step -0.5 hours |
|
Correction of the air sensor temperature (correction). If it is necessary to correct the temperature sensor reading on the controller screen |
Hold down the middle key for 3 s. Navigate through the menu – middle key, change the parameter with “+” and “-“ |
COr 0.0(zero) tС (ºC) |
0ºC |
±5ºC, step 0.1ºC |
|
Resistance humidity (resistance humidity) |
Hold down the middle key for 3 s. Navigate through the menu – middle key, change the parameter with “+” and “-“ |
rXu 200(two hundred) r (units) |
200 unit. |
10-990, step 10 |
|
Service information |
||||
|
Total operating time of the heater (hours) |
Hold down the middle key for 6 s |
h
5.0 |
To view |
|
|
Firmware version preview |
Hold down the middle key for 12 s |
SnG 2.1 |
To view |
|
|
Heating relay switch-on counter |
Hold down the middle key for 15 s |
r 9 |
To view |
|
|
Controller switch-on counter |
Hold down the middle key for 18 s |
I 6 |
To view |
|
|
Factory reset |
Hold down the middle key for 30 s |
dEF |
After releasing the key, the controller will reset all settings to factory defaults |
|
Procedure for forced switching on of the electric heating system ( if it is necessary to switch on the system in the absence of precipitation,
factory value – 3 hours)
- Press the middle key once to switch on/off forcibly. After switching on, the middle screen will show the time left until the heating is finished. With “+” and “-” you can change the heating time in the range of 0.5-9 hours, step 0.5 hours
Weather station (temperature regulator) Terneo sneg

Upper/lower temperature limits
(factory settings 5ºC/-10ºC)
To view the upper temperature limit, briefly press “+”, the lower limit – “-“. The flashing value of the borders can be changed with the “+” and “-” keys. 3 s after the last key press the controller returns to the normal operating mode
Functional menu
|
Function menu item |
Setting procedure |
Value on the screen |
Factory settings |
Change with the “+” and “-” keys |
|
Settings menu |
||||
|
Postheat time (postheat). After the end of precipitation, the heating will continue for the set value |
Hold down the middle key for 3 s. Navigate through the menu – middle key, change the parameter with “+” and “-“ |
Pht 2.0(two) H (hours) |
2 hours |
0.5-9 hours, step -0.5 hours |
|
Correction of the air sensor temperature (correction). If it is necessary to correct the temperature sensor reading on the controller screen |
Hold down the middle key for 3 s. Navigate through the menu – middle key, change the parameter with “+” and “-“ |
COr 0.0(zero) tС (ºC) |
0ºC |
±5ºC, step 0.1ºC |
|
Resistance humidity (resistance humidity) |
Hold down the middle key for 3 s. Navigate through the menu – middle key, change the parameter with “+” and “-“ |
rXu 200(two hundred) r (units) |
200 unit. |
10-990, step 10 |
|
Service information |
||||
|
Total operating time of the heater (hours) |
Hold down the middle key for 6 s |
h
5.0 |
To view |
|
|
Firmware version preview |
Hold down the middle key for 12 s |
SnG 2.1 |
To view |
|
|
Heating relay switch-on counter |
Hold down the middle key for 15 s |
r 9 |
To view |
|
|
Controller switch-on counter |
Hold down the middle key for 18 s |
I 6 |
To view |
|
|
Factory reset |
Hold down the middle key for 30 s |
dEF |
After releasing the key, the controller will reset all settings to factory defaults |
|
Procedure for forced switching on of the electric heating system ( if it is necessary to switch on the system in the absence of precipitation,
factory value – 3 hours)
- Press the middle key once to switch on/off forcibly. After switching on, the middle screen will show the time left until the heating is finished. With “+” and “-” you can change the heating time in the range of 0.5-9 hours, step 0.5 hours